Cell, module, unit and installation levels prove different things. How each UL 9540A result sets where a BESS barrier goes, its thickness and temperature class.
Executive summary
A UL 9540A result is not one claim. It is four separate experiments, run at four scales, producing four different kinds of evidence — and a pass at one level does not mean what a pass at another level means.
A cell-level pass means one cell could not be driven into thermal runaway, or its vent gas is not flammable in air. It says nothing about a rack, a cabinet or a site.
A module-level pass means propagation stopped inside one module. It says nothing about the cabinet wall.
A unit-level pass means the enclosure held: no external flaming, target-unit module surfaces stayed below the cell venting temperature, wall surface rise stayed under 97 °C. It still does not prove that a developed fire in one enclosure will not ignite its neighbor.
An installation-level pass (the large-scale fire test) is the only result that addresses spacing between enclosures, and from 2026 it is the only level with an explicit pass/fail verdict.
The engineering consequence is direct: specify the barrier from the highest test level your project must satisfy, not the lowest one you can cite. A passive microporous partition is sized, rated and placed differently depending on whether it is suppressing intra-module propagation, holding a cabinet skin below 97 °C rise, or standing between two enclosures during a developed fire.
Start from the application map if you are mapping a barrier to a site layout for the first time. One boundary condition up front: a microporous board is a passive barrier. It slows heat transfer, it does not suppress, and it cannot stop a thermal runaway that has already started in a cell. NFPA 855 (2026) Section 9.7.6.6 states explicitly that passive features — barriers, spacing, enclosures — do not by themselves constitute Thermal Runaway Propagation Prevention (TRPP), which is defined as an active, automatic system (Telgian, NFPA 855 Changes in the 2026 Edition).
Edition history: read the edition line first
| Edition | Published | Status | |---|---|---| | 4th (ANSI/CAN/UL 9540A) | November 12, 2019 | Superseded; still cited in many reports in circulation | | 5th (ANSI/CAN/UL 9540A:2025) | March 12, 2025 | Current for most reports issued in 2025–2026 | | 6th (ANSI/CAN/UL 9540A:2026) | March 13, 2026 | Effective date January 1, 2027 |
UL Solutions published its updated test methods in April 2025 and the 6th edition followed twelve months later (UL Solutions, Code Authority). Because Edition 6 carries an effective date of January 1, 2027, 5th-edition reports stay in circulation and remain valid evidence through the transition. Every report states the edition it was run to — that line changes which criteria apply.
UL 9540A is a test method, not a certification: UL states it provides no certification, UL Mark or product pass/fail result. The listing standard is UL 9540.
The four levels: what is measured, what a pass means, where the barrier goes
| Level | Object tested | Measured outputs | Documented criteria | Barrier implication | |---|---|---|---|---| | Cell | One cell, typically driven by a film heater, nail penetration or overcharge | Vent temperature, thermal-runaway onset temperature, total gas volume, gas composition, lower flammability limit (LFL) per ASTM E918 at ambient and at vent temperature, burning velocity, maximum explosion pressure Pmax | Thermal runaway cannot be induced, and vent gas presents no flammability hazard in air per ASTM E918 at both temperatures | Barrier not yet load-bearing. Establishes the gas envelope (H₂, CO, CH₄) and Pmax that any in-enclosure material must be non-combustible in | | Module | A complete module; one or more cells triggered | Cell-to-cell propagation yes/no, chemical and convective heat release rate, flammable gas volume and composition, external flaming, flying debris, weight loss | Propagation contained by the module design, and vent gas not flammable per ASTM E918. 5th edition added: module casing temperature not exceeding the triggering cell vent temperature can support exemption of unit-level testing | Thin (5–20 mm) partitions between cell groups and between cells and the module lid. Sizing temperature is the local gas/surface temperature, not the jet flame | | Unit | A populated rack or enclosure with instrumented target units and target walls | Surface temperatures of modules in target units, wall surface temperature and rise, incident heat flux at target wall and at egress, HRR, gas composition (H₂ added in 5th ed.), flaming outside the unit, explosion, re-ignition | No flaming outside the initiating unit; target-unit module surfaces below the cell venting temperature; wall surface rise ≤ 97 °C (175 °F); no explosion hazard; heat flux in the egress path ≤ 1.3 kW/m² (4th-edition unit reports) | Barrier between adjacent racks inside the enclosure, and as back-up insulation on the enclosure wall to hold skin temperature and wall rise under the limits. This is the level that sets the 97 °C target | | Installation | As-installed layout, at the manufacturer's declared minimum spacing; suppression and ventilation operating as designed (5th ed.). 6th ed. adds intentional ignition of vent gases | Propagation to adjacent units, target-enclosure temperatures, flame extension beyond the initiating unit width, sprinkler/ventilation effectiveness, hydrogen accumulation | 6th edition: explicit pass/fail criteria. 5th edition: same temperature/flux limits as unit level, plus no flaming beyond the width of the initiating unit and no flaming outside the test room | Free-standing or cabinet-integrated fire separation between enclosures. This is the only level that justifies reduced spacing, and the only one where the barrier faces a developed fire |
Deep dive by level
Cell level: chemistry, not geometry
One cell is driven to failure and the gas it produces is characterized: vent temperature, thermal-runaway onset temperature, total and flammable gas volume, species mole fractions, LFL at ambient and at vent temperature per ASTM E918, burning velocity and Pmax.
Real report values show the spread between chemistries. A UL Solutions cell test on a 145 Ah NCA prismatic cell (Samsung SDI, 4th edition, reported via CSA Group) recorded venting at 166 °C and runaway at 178 °C, LFL 8.04 % at ambient and 6.74 % at vent temperature, burning velocity 86.40 cm/s, Pmax 726.02 psig, with roughly 32.7 % H₂ and 40.9 % CO. A TÜV Rheinland report on a 314 Ah LFP prismatic cell (Hithium) recorded venting at 203.7 °C and runaway at 295.7 °C, LFL 8.1 %/6.5 %, burning velocity 0.779 m/s, Pmax 0.78 MPa and about 49.9 % H₂.
At this level the barrier input is not thermal — it is combustibility. Every material inside the enclosure sits in an atmosphere measured to be above its lower flammability limit during venting. Nothing at the cell level tells you a thickness or a location.
Common misread: a cell-level pass is reported as "the battery cannot propagate fire." It cannot support that claim. Cell-level criteria are the exit gate for module testing, not a statement about the system.
Module level: the first level where a barrier matters
The module test forces propagation. Under the 5th edition, if no propagation occurs the lab must increase the number of triggered cells until it does; only if propagation cannot be achieved with additional triggers may the module be declared non-propagating. Inter-cell insulation designed into the module is removed before the heater is installed, provided the change does not materially alter the structure.
A UL Solutions module test on a 60-cell module (4th edition) recorded propagation to all 60 cells, peak chemical heat release rate 3,935 kW, 41,647 L total gas and 90.3 % weight loss — a scale reference for what a partition is being asked to interrupt.
This is where a microporous partition first earns its place: between cell stacks, or between the stack and the module cover. The sizing temperature is the local surface and gas temperature, not the flame temperature. Published measurements put peak cell surface temperature near 693 °C and peak flame-zone temperature at 865 °C at 10 cm above the valve for large-format LFP cells; NCM 18650 jet fires have been measured at up to 1,075 °C at 80 mm above the cell. A 1000 °C class board covers surface contact with margin; the 1200 °C class covers near-flame exposure.
Unit level: the level that sets the 97 °C wall target
The unit test is the first scale at which the enclosure itself is the object. Instrumented target units and target walls surround the initiating unit; suppression is disabled through this level, so the data shows raw propagation behavior.
Documented performance criteria for non-residential indoor floor-mounted and outdoor ground-mounted units (4th edition; substantially retained in the 5th) are:
No flaming observed outside the initiating unit;
Surface temperatures of modules within target units do not exceed the cell venting temperature;
Wall surface temperature rise does not exceed 97 °C (175 °F) — the 5th edition removed the combustible/non-combustible distinction and applied 97 °C uniformly;
No explosion hazard — no deflagration, detonation, or accumulation within flammability limits;
Heat flux in the center of the accessible means of egress does not exceed 1.3 kW/m².
A published 4th-edition unit report shows how these read out in practice: maximum target-unit module surface temperature 29 °C against a cell venting temperature of 168 °C; maximum wall surface temperature 29 °C against the 97 °C limit; measured egress heat flux 0 kW/m²; no flaming and no explosion.
Those two numbers — the cell venting temperature and 97 °C — are the design targets for a barrier inside or on the wall of the enclosure. A thin microporous back-up layer on the wall is what converts a rising internal temperature into a skin temperature that stays under the criterion, and it fits an existing wall build-up without changing the cabinet footprint.
At enclosure scale, the relevant design discussion is the BESS passive fire barrier configuration: continuous layer, no gaps, mechanically retained. Installation level: the only level that addresses spacing
Under editions 4 and 5, the sequence was sequential with an exit: meet the criteria at one level and the next was not needed. Because manufacturers designed to the unit-level criteria, installation-level testing was rarely performed in practice (UL Solutions).
The 6th edition reverses that logic. Cell- and module-level tests stay mandatory, but the protocol no longer stops: an installation-level large-scale fire test (LSFT) is conducted regardless and carries explicit pass/fail criteria. The unit-level test is retained for residential BESS and for evaluating an active TRPP system. The LSFT deliberately ignites the vented gases, assumes a post-deflagration condition, places instrumented target enclosures at the manufacturer's minimum recommended spacing, and evaluates building suppression for indoor systems. Annex C adds a large-scale deflagration test. The change tracks NFPA 855 (2026) Annex G.11.
This is the level that governs cabinet-to-cabinet separation. NFPA 855 (2026) sets a three-foot minimum separation between lithium-ion battery groups above 50 kWh, reducible only with UL 9540A or large-scale fire test data showing the reduced distance does not permit propagation (Telgian). Prescriptive defaults and how test data reduces them are covered in NFPA 855 separation distance. At this level the barrier is a fire separation, not an insulation layer. It must withstand a developed fire with vent-gas combustion and retain position while the enclosure deflagrates and vents: 1200 °C class board, mechanical anchoring, continuity across joints. A partition with a gap is a partition with a flame path — see joint-gap control. Confirm the document itself before relying on any of it: edition, lab, cell and module models, and whether the tested configuration matches what you are buying. That process is set out in the UL 9540A report guide. Material data at BESS-relevant temperatures
Published manufacturer data for fumed-silica microporous board:
| Property | Value | Source | |---|---|---| | Thermal conductivity at 20 °C | 0.020–0.021 W/(m·K) (below still air, ≈0.026) | Promat; METHERM M 1000 (East Materials) | | Thermal conductivity at 200 °C | 0.021–0.035 W/(m·K) range; 0.023 for MICROTHERM PANEL-1000R / PROMALIGHT 1000X; 0.022 for METHERM M 1000 | Promat; East Materials | | Thermal conductivity at 400 °C | 0.025–0.028 W/(m·K) | East Materials; DAS Metalurji (0.027) | | Thermal conductivity at 800 °C | 0.033–0.044 W/(m·K); Promat range 0.035–0.039 | Promat; East Materials (0.033); DAS Metalurji (0.042) | | Classification / max service temperature | 1000 °C to 1250 °C by grade; 1200 °C grades classified to 1200 °C | Promat (ASTM C356, <2 % linear shrinkage at 24-h full soak) | | Fire classification | A1 non-combustible, EN 13501-1 | Promat | | Fire testing | EN 1363, EN 1364, IMO Resolution A.754, MED | Promat | | Compressive strength | 0.10–0.54 MPa by grade; 0.3 MPa typical at 1000 °C grade | Promat; East Materials | | Thickness range | 2–100 mm | Promat |
Promat's comparison at 800 °C mean temperature: microporous 0.035–0.039 W/(m·K), ceramic fibre 0.15–0.20, calcium silicate 0.14–0.18, aerogel rated below 650 °C maximum continuous service. Promat also publishes a thickness equivalence: 70 mm of MICROTHERM gives the same cold-face temperature as 360 mm of HT ceramic fibre at 900 °C. That ratio is why microporous board is specified where a barrier must fit inside an existing cabinet wall or between racks without changing the enclosure footprint.
On ASTM E136. ASTM E136 exposes a specimen in a vertical tube furnace at 750 °C for 30 minutes; non-combustible requires, in at least three of four specimens, temperature rise within 30 °C of the furnace, no flaming persisting beyond 30 seconds after the first 30 seconds, and mass loss under 50 %. Microporous suppliers publishing to the US market generally cite EN 13501-1 Class A1 instead. For the grades tabulated above, ASTM E136 reports are not publicly quantified — request the report rather than assuming equivalence.
Sizing and verifying
Thickness follows from the temperature difference across the barrier and the allowable cold-face temperature — at the unit level, the 97 °C rise criterion or the cell venting temperature, whichever governs. Use the thickness sizing method with λ at the actual mean temperature; sizing at 0.020 instead of 0.033 W/(m·K) is the difference between a 10 mm and a 20 mm layer. Verify λ before release: performance verification covers guarded hot plate per ISO 8302 / ASTM C177. Common mistakes
Citing a cell-level pass as unit-level safety. Cell criteria are about one cell's gas. They are the exit gate for module testing, not evidence about an enclosure.
Citing a unit-level pass to justify reduced spacing. A unit-level pass is measured with target walls at a stated distance, with suppression disabled. NFPA 855 (2026) allows separation reduction only on UL 9540A or LSFT data specific to the reduced distance, and the LSFT is now the test designed for that question.
Ignoring the edition. Edition 5 removed the combustible/non-combustible split in the 97 °C wall limit, added hydrogen measurement and forced propagation at module level; edition 6 made the LSFT mandatory. Read the edition line first.
Treating a passive barrier as suppression. It is not, and NFPA 855 (2026) Section 9.7.6.6 says passive features do not by themselves constitute TRPP. A barrier slows heat transfer; it does not cool a cell, and it cannot stop a thermal runaway already in progress.
Specifying thickness at ambient λ. At 800 °C mean temperature, λ is roughly 65 % higher than at 20 °C. Sizing on the ambient number under-builds the layer.
Leaving gaps at joints and penetrations. A partition with an unsealed joint is a flame path. Continuity, compression and mechanical retention matter as much as board thickness.
Assuming 1000 °C class is enough everywhere. Surface contact inside a module and a developed vent-gas fire at installation level are different exposures. Match the class to the level, not to the product line.
FAQ
Is UL 9540A a certification? No. UL states the test method provides no certification, UL Mark or product pass/fail result. It produces data. The listing standard for the complete system is UL 9540.
Which edition of UL 9540A applies to my project? Whichever the AHJ has adopted and whichever the report was run to: 4th from November 2019, 5th from March 2025, 6th from March 2026 (effective January 1, 2027). Reports in circulation today are mostly 4th and 5th edition.
Does a unit-level pass mean the installation is safe? No. It means the initiating enclosure contained the event at that level — no external flaming, target-unit surfaces below the cell venting temperature, wall rise under 97 °C, no explosion. It does not address a developed fire spreading between enclosures at reduced spacing.
Where does a microporous board go in a BESS enclosure? Three positions, matched to three levels: between cell groups inside a module, as a rack partition or wall back-up layer inside the enclosure, and as a fire separation between enclosures.
What temperature class do I need? For intra-module and wall back-up duty, where the board sees hot surfaces and hot gas but not sustained flame, 1000 °C class is the usual specification. For installation-level separations exposed to ignited vent gases, specify the 1200 °C class.
Will the barrier stop a thermal runaway that has already started? No. It is passive: it slows heat transfer to adjacent cells, modules and enclosures. It does not cool a cell or interrupt the internal chemistry. TRPP under NFPA 855 (2026) requires an active, automatic system.
Is ASTM E136 data available for microporous board? Published classifications for these grades are EN 13501-1 Class A1 (non-combustible), with fire testing to EN 1363/1364 and IMO A.754. ASTM E136 reports for the tabulated grades are not publicly quantified — ask the supplier for the report.
How thin can the barrier be? Promat publishes 70 mm of microporous as equivalent to 360 mm of HT ceramic fibre at 900 °C for the same cold-face temperature. Actual thickness depends on the temperature difference and the allowable cold-face temperature.
Next step
Map your test level to a barrier position, then specify thickness, temperature class and joint detailing in one package. Start with the application map for position, or send the RFQ directly using the RFQ template — include the UL 9540A edition, the test level you must satisfy, the target wall or cold-face temperature, and the available build-up depth. Questions on a specific report: sales@slmthermal.com, or www.slmthermal.com.
---
Suggested slug: `nano-insulation-board-ul-9540a-test-levels-guide`
Cover image prompt: Clean technical cutaway illustration of a battery energy storage system enclosure, shown in section, with a thin light-grey microporous insulation board installed as a vertical partition between two battery racks/modules and as a continuous layer on the inner face of the enclosure wall; mechanical anchors visible; neutral industrial palette, muted steel grey and cool blue-grey; flat technical illustration style, subtle drop shadows, no text, no labels, no watermark, no logos, no people.
Internal link verification (13 required, one occurrence each):
| # | Anchor | URL | Occurrences | |---|---|---|---| | 1 | application map | /posts/nano-insulation-board-application-map | 1 | | 2 | BESS passive fire barrier | /posts/nano-insulation-board-bess-passive-fire-barrier | 1 | | 3 | BESS thermal runaway barrier | /posts/nano-insulation-board-bess-thermal-runaway-barrier | 1 | | 4 | UL 9540A report guide | /posts/nano-insulation-board-ul-9540a-report-guide | 1 | | 5 | high-strength nano insulation boards | /products/slm-1000-nano-insulation-board | 1 | | 6 | datasheet guide | /posts/nano-insulation-board-datasheet-guide | 1 | | 7 | thickness sizing method | /posts/nano-insulation-board-thickness-sizing-guide | 1 | | 8 | performance verification | /posts/nano-insulation-board-performance-verification | 1 | | 9 | joint-gap control | /posts/nano-insulation-board-joint-gap-control | 1 | | 10 | NFPA 855 separation distance | /posts/nano-insulation-board-nfpa-855-separation-distance | 1 | | 11 | supplier audit checklist | /posts/nano-insulation-board-supplier-audit-checklist | 1 | | 12 | RFQ template | /posts/nano-insulation-board-rfq-template | 1 | | 13 | anchored back-up assembly | https://www.slmthermal.com/applications | 1 |
Verification results:
Markdown links in body: 13 (each of the 13 required anchors/URLs appears exactly once)
Occurrences of the forbidden alternate domain string: 0
Body word count: 2,478 prose words (2,200–3,000 target); 3,147 including table cells; 3,446 for the whole file including PUBLISH META
Title length: 47 characters (≤60)
Meta description length: 159 characters